Drives Inverters Guides • PLC Guides

PLC Keyence “Modbus RTU” LS iG5A VFD Tutorial

Written by October

Continuing with the series of articles on how to control LS iG5A VFD via Modbus-RTU (RS485) communication standard, today plc247.com would like to continue to guide you to use PLC Keyence to control

We can use any Keyence PLC of KV-Series in combination with Module KV-L21/21V to connect.

Keyence KV-L21V & LS iG5A VFD Connection Diagram

LS iG5A Configurator

In addition to the basic parameters for the motor installation, we need to set the communication parameters according to the following table

+ Drv = 3

+ Frq = 7

+ I59 = 0

+ I60 = 1

+ I61 = 3

+ I62 = 0

+ I65 = 2

Modbus Regigter Address

Note: PLC Register Address = “Address – 1”

PLC Keyence Modbus RTU Configurator

We need to set the same parameter as the inverter

KV5500 PLC Programming

+ Reset registers when PLC starts running & Control Read/Write

+ Frequency Write Command

+ Control Run Command

+ Read Data Command

+ Read Data Reponse

Video Installing and Running the Program

======

Required documents and software:

+ KV Studio for PLC Keyence Programming

+ LS iG5A VFD Manual PDF Download (Password Extract: plc247.com)

If you need any support, please comment below the article, plc247.com will reply to you as soon as possible.

Best Regards!

About the author

October

Leave a Comment